A concentric reducer keeps both ends on one centerline. An eccentric reducer offsets them, leaving one side flat. That difference affects pipe alignment, air accumulation and drainage at a size transition.
Quick rule of thumb: use a concentric reducer for vertical pipe transitions where centerline alignment is required. For horizontal pump suction piping, an eccentric reducer with the flat side up (FOT) is the usual choice. Use flat on bottom (FOB) where the design needs a continuous lower pipe profile, such as a sloped steam main or a pipe rack with a common bottom elevation.
What Is the Difference Between Concentric and Eccentric Reducers?
A concentric pipe reducer has a symmetrical transition between its large and small ends. Both openings share the same centerline. An eccentric pipe reducer has an asymmetrical transition: its end centerlines are offset, and one side remains straight. This allows the top or bottom of connected pipes to stay at a common elevation.
| Feature | Concentric Reducer | Eccentric Reducer |
|---|---|---|
| Centerlines | Aligned | Offset |
| Transition | Symmetrical | Asymmetrical, with one straight side |
| Main layout benefit | Maintains pipe centerline | Maintains a common top or bottom profile |
Which Reducer Should You Use? A Quick Selection Guide
Start with the pipe orientation and the location of potential air or liquid pockets. The table below covers common applications.
| Application | Typical Choice | Reason |
|---|---|---|
| Vertical pipe transition | Concentric | Keeps the pipe centerlines aligned |
| Horizontal pump suction | Eccentric, FOT | Helps prevent air or vapor accumulation at the transition |
| Pump suction approaching from above | Concentric or eccentric, FOB | Supports the required descending suction profile |
| Sloped horizontal steam main | Eccentric, FOB | Maintains bottom slope for condensate drainage |
| Pipe rack with common bottom elevation | Eccentric, FOB | Preserves the bottom-of-pipe elevation |
| Pump discharge or general size transition | Often concentric | Maintains centerline alignment where the flow arrangement permits |
ANSI/HI 9.6.6-2022 provides guidance on reducers in horizontal pump suction piping, including arrangements used when the suction line approaches from above. For a specific installation, follow the approved piping design and pump manufacturer's instructions.
When to Use a Concentric Reducer
Choose a concentric reducer when both pipes should share the same centerline. Vertical transitions are a common example. A concentric reducer can also work in a horizontal line when its geometry does not create a troublesome air or liquid pocket.
Pump discharge piping commonly uses concentric reducers. Aligned centerlines simplify the connection, and air trapping is generally less of a concern than on the suction side. Check the selected fitting against the nozzle size and discharge piping layout.
KSB notes that for some axially split casing pumps, a concentric reducer gives a more even inlet flow distribution when air accumulation is not expected. This matters particularly in certain double-suction pump arrangements, where uneven flow can affect pump performance.
Eccentric Reducer Orientation: Flat Side Up or Down?
Flat side up maintains a continuous upper pipe profile to help prevent air pockets. Flat side down maintains a continuous lower profile to support drainage. On piping drawings, these arrangements are identified as flat on top (FOT) and flat on bottom (FOB). The terms describe the straight side of the reducer, not the direction of flow.
Flat Side Up (FOT): Horizontal Pump Suction
For horizontal pump suction piping, FOT is the usual arrangement. It avoids the raised upper profile that a concentric reducer could create when connecting a larger suction pipe to a smaller pump nozzle. Air or vapor may otherwise collect near the transition and disturb the flow entering the pump.
A correctly oriented reducer cannot compensate for a poor suction layout. Inadequate straight pipe, a poorly positioned elbow or excessive suction losses can also affect pump operation. ANSI/HI 9.6.6 provides guidance on these piping arrangements.
Flat Side Down (FOB): Suction Piping Approaching from Above
When suction piping approaches a horizontal pump from above, ANSI/HI 9.6.6 describes an arrangement using a concentric reducer or an eccentric reducer with its flat side down. For some axially split casing pumps, KSB shows a flat-side-down eccentric reducer with the suction line sloping toward the pump.
Look at the complete inlet profile. Air or vapor needs a path out of the suction line rather than an isolated pocket near the pump.
Flat Side Down (FOB): Steam Mains and Condensate Drainage
In sloped horizontal steam mains, an eccentric reducer with its flat side down maintains the bottom pipe profile. This helps condensate drain instead of collecting at a size transition. Standing water in a steam main increases the risk of water hammer.
University of Maryland's steam-piping specifications call for eccentric reducers with the level side down at pipe-size transitions. This arrangement preserves the lower pipe profile and supports condensate drainage. Drain points and pipe slope are equally important to the drainage design.
Pipe Racks and Other Horizontal Lines
An eccentric reducer installed flat side down keeps the bottom-of-pipe elevation consistent across a pipe rack. This can simplify support arrangements and preserve the intended drainage slope.
For horizontal lines, check what may collect at the transition. A continuous upper profile helps avoid trapped gas in liquid piping; a continuous lower profile helps drain accumulated liquid. In two-phase service, the reducer orientation must match the pipe slope and the intended gas and liquid flow paths.
How to Calculate Eccentric Reducer Centerline Offset
For an eccentric reducer with one straight external side, the nominal centerline offset is half the difference between the large-end and small-end outside diameters (OD).
Centerline Offset = (Large-End OD − Small-End OD) ÷ 2
| Reducer Size | Large-End OD | Small-End OD | Centerline Offset |
|---|---|---|---|
| NPS 4 × 3 | 4.500 in | 3.500 in | 0.500 in (12.7 mm) |
| NPS 6 × 4 | 6.625 in | 4.500 in | 1.0625 in (27.0 mm) |
| NPS 2 × 1 | 2.375 in | 1.315 in | 0.530 in (13.5 mm) |
Take an NPS 4 × 3 eccentric reducer. The two pipe outside diameters are 4.500 in and 3.500 in. Their difference is 1.000 in, giving a centerline offset of 0.500 in (12.7 mm). Using the full 1.000 in diameter difference as the offset would double the correct value.
The table uses nominal pipe outside diameters. For fabrication or installation, check the reducer drawing for specified dimensions and tolerances. To identify nominal pipe size from an actual measurement, see How to Measure Pipe Size.
Reducer Standards and How to Specify One
ASME B16.9-2024, Factory-Made Wrought Buttwelding Fittings, covers concentric and eccentric butt-weld reducers. It specifies requirements for dimensions, tolerances, ratings, testing and marking. Threaded reducers and other connection types may follow different standards.
A complete reducer specification should identify:
Nominal large-end and small-end sizes, such as NPS 4 × NPS 3.
Concentric or eccentric geometry, including FOT or FOB where required.
Connection type, dimensional standard and wall thickness or schedule.
Material grade, design pressure, temperature and service fluid.
Installation requirements, available space and pipe support conditions.
For example: “Eccentric reducer, NPS 4 × NPS 3, butt-weld, ASME B16.9, ASTM A234 WPB, Sch 40 × Sch 40, FOT as shown on the approved piping drawing.” Confirm dimensions against the manufacturer's product specification before ordering.
Related Pipe Size-Reducing Fittings at LILY Bearing
LILY Bearing also lists other pipe fittings for connecting different nominal sizes. These products use threaded connections rather than the butt-weld concentric or eccentric reducer designs discussed above.
For example, the HIBIKCBD galvanized steel reducing pipe nipple connects 3/4 in and 1/4 in nominal NPT pipe sizes using male threads at both ends. It is listed as Schedule 80. The FDCDNEH galvanized iron reducing bushing provides a 2 1/2 in × 2 in nominal size transition with NPT male and female threads. These are examples of threaded size-reducing connections, not direct substitutes for an ASME B16.9 butt-weld reducer.
For other materials and connection styles, browse the LILY Bearing pipe fittings catalog. The iron and steel unthreaded pipe and fittings and stainless steel unthreaded pipe and fittings categories cover related nonthreaded piping components. Check individual product specifications for geometry, dimensions and connection type.
For an overview of pipe connections and size transitions, see Types of Pipe Fittings.
Frequently Asked Questions
Does an Eccentric Reducer Prevent Cavitation?
No. An eccentric reducer installed correctly can help avoid air pockets and poor suction geometry, but it cannot guarantee freedom from cavitation. Cavitation also depends on available net positive suction head (NPSH), fluid temperature, pressure losses and pump operating conditions.
Are Concentric and Eccentric Reducers Interchangeable?
They can have identical nominal end sizes, materials and connection styles, but their centerline geometry differs. Replacing one with the other changes pipe alignment and may introduce an unwanted high or low point. Review the piping layout before making a substitution.
Can an Eccentric Reducer Be Installed Vertically?
Yes. A concentric reducer is usually preferred for a vertical pipe transition because it maintains centerline alignment. An eccentric reducer is useful when the layout requires an offset.
KSB notes that an eccentric reducer at the inlet of certain vertically installed double-suction pumps can produce uneven flow distribution. The pump manufacturer's specified inlet arrangement should take precedence.
How Much Pressure Drop Does a Pipe Reducer Cause?
A reducer introduces a local flow loss. For incompressible flow, estimate the head loss using:
hL = K × v² / (2g)
Convert the head loss to the corresponding pressure loss with:
ΔP_loss = ρ × g × hL
Here, hL is the local head loss, K is the fitting loss coefficient, v is the reference flow velocity, ρ is fluid density and g is gravitational acceleration. Use consistent units and the velocity basis specified with the selected K value. Depending on the method, that basis may refer to the upstream or downstream pipe.
The loss depends on the diameter ratio, transition geometry, flow direction and operating conditions. Engineering fluid mechanics references, including Southern Illinois University's laboratory manual, explain how fitting loss coefficients are used. The total static pressure change across a reducer also includes the effects of velocity change and elevation difference.
Technical References
ASME B16.9-2024 — Factory-Made Wrought Buttwelding Fittings. Dimensional and manufacturing requirements for wrought butt-weld fittings.
Hydraulic Institute — ANSI/HI 9.6.6-2022, Rotodynamic Pumps for Pump Piping. Guidance on pump suction and discharge piping arrangements.
Missouri State University — Blunt Hall Addition and Renovation, Construction Specifications, Volume 4, Section 21 30 00, Fire Pumps. Requirements for flat-on-top eccentric reducers at pump suction flanges. University construction specifications (PDF).
University of Maryland — Section 33 63 00, Underground Thermal Energy Distribution Piping and Manholes, Piping Installation. Guidance on steam piping slopes and flat-side-down eccentric reducers. University engineering specifications.
Southern Illinois University — Engineering Fluid Mechanics Laboratory Manual, Minor Loss Experiment. Loss coefficients and the distinction between fitting head loss and pressure changes across contractions and expansions. Engineering Fluid Mechanics manual (PDF).
Need Help Matching a Reducer?
Need a size-changing pipe fitting for an existing connection? Contact LILY Bearing with the large and small nominal sizes, material, wall thickness, connection type and relevant drawings. For concentric or eccentric butt-weld reducers, specify the required geometry and installation orientation so the correct product configuration can be assessed.